Check the Current. If it is under 4 mA or over 20mA, the gateway will report UNAVAILABLE. Change the current range by tapping Setup > Extended Functions > Current Output > Current Range > Set it to 4 to 20. If it is set to 3.8 to 20.5 causes issues when the sensor reads below the MIN value
CNCR Analog sensor reporting unavailable to Gateway/BinCloud.